What Is a Mixed-Use Building? Article 18 of the Fire Regulation, Occupancy Classes, Fire Compartment and Business Licence

SUMMARY
A mixed-use building is one of the occupancy classes listed in Article 8 of the Binaların Yangından Korunması Hakkında Yönetmelik (Regulation on Fire Protection of Buildings). Under Article 18, if sections of different classes cannot be separated by a fire compartment suitable for the higher hazard class, the rules requiring the higher level of protection apply to the whole building.
In this article the occupancy classes, the criterion in Article 18, the provisions tying sections to the class of the main building, the fire compartment and fire wall rules and the link with the business licence are given with verbatim quotations from the regulation.
For the sales center authorization certificate application and your ÜTS registrations after the business licence: Medical Device ÜTS Registration Consultancy
Contents
1. Occupancy Classes: Article 8
The Regulation on Fire Protection of Buildings (2007/12937) classifies buildings according to their use characteristics:
“ARTICLE 8- (1) The classes of buildings according to their use characteristics are as follows:”
“(a) Residential buildings,”
“(b) Accommodation buildings,”
“(c) Institutional buildings,”
“(ç) Office buildings,”
“(d) Commercial buildings,”
“(e) Industrial buildings,”
“(f) Assembly buildings,”
“(g) Storage facilities,”
“(ğ) High-hazard places,”
“(h) Mixed-use buildings.”
The procedure to follow in case of doubt about the class is in the second paragraph of the same article:
“(2) Where any doubt arises concerning the occupancy class of buildings, the assessment and decision of the Ministry of Environment, Urbanisation and Climate Change shall be followed.”
2. The Mixed-Use Criterion: Article 18
“ARTICLE 18- (1) Where a building has sections that are subject to two or more occupancy classifications, and these sections cannot be separated from one another by a fire compartment suitable for the higher hazard class, or it is not possible to apply separate protective measures because they are interlocked, the rules relating to the classification requiring higher protective measures shall be applied to the whole building.”
Under the article, the rules requiring higher protective measures apply to the whole building if one of two conditions exists:
The building has sections subject to two or more occupancy classes, and these sections cannot be separated from one another by a fire compartment suitable for the higher hazard class.
Or it is not possible to apply separate protective measures because the sections are interlocked.
The expression "mixed use" also appears in Article 51 of the Regulation:
“(2) (Amended: 10/8/2009-2009/15316 Decision) In mixed-use buildings, at least half of the number and capacity of the required exits of theatres, cinemas or concert halls must be considered within their own compartment.”
3. Provisions Tying Sections to the Class of the Main Building
The Regulation does not treat some sections as a separate class but ties them to the class of the main building. Article 12, for office sections:
“(2) Sections used for office services within another building are subject to the occupancy classification of the main building.”
The second paragraph of Article 13 sets two rules for commercial sections:
“(2) Office, storage and service sections located within the same building and used in connection with the sale of commercial goods fall into the commercial building class. Small commercial sections located in a building that primarily falls into another occupancy class are subject to the provisions on the primary occupancy classification of the building.”
Article 15, for assembly sections:
“(2) Sections used for assembly purposes in any building, but suitable for the gathering of fewer than 50 people, are subject to the occupancy classification of the main building.”
Article 16, for storage sections:
“(2) Storage sections smaller than 50 m² located within a building are considered part of the main building.”
4. Definition of the Health, Office and Commercial Classes
Definitions of three classes frequently encountered in the medical device and healthcare sector. Office buildings, Article 12:
“ARTICLE 12- (1) Office buildings are buildings, other than those within the scope of commercial buildings, in which all kinds of office services are carried out for business purposes and accounting, recording and similar work is done. Banks, stock exchanges, public service buildings, general office buildings and places such as the offices of doctors and dentists are among these buildings.”
Commercial buildings, Article 13:
“ARTICLE 13- (1) Commercial buildings are places where food, clothing, health and other necessities are sold wholesale and retail. Shops, stores, markets, supermarkets, wholesale complexes, vegetable, fruit and fish markets, meat exchanges, covered bazaars, arcades, repair shops, spare parts and materials sales outlets and similar places are commercial buildings.”
Healthcare buildings are defined within institutional buildings, in point (b) of Article 11:
“(b) Healthcare buildings: These cover buildings, or the parts of buildings used for this purpose, in which the treatment or care of a physical or mental illness or disability is provided, or which are used for the care of small children, convalescents or elderly people in need of care, and in which four or more people can be accommodated. Hospitals, nursing homes, child care and rehabilitation centres, dispensaries and similar places fall into this class. Health centres, private clinics, infirmaries, diagnosis and treatment centres and medical laboratories are also counted in this class.”
The Annex-4 table gives the maximum compartment area by class: 1500 m² in healthcare buildings, 8000 m² in office buildings and 2000 m² in commercial buildings. According to the notes to the table, these areas can be increased if suitable fire control systems are in place:
“(1) Where suitable fire control systems (automatic detection, sprinkler system, smoke exhaust system and the like) have been installed in buildings, the compartment area may be doubled.”
“(2) Where suitable fire control systems (automatic detection, sprinkler system, smoke exhaust system and the like) have been installed in buildings, the compartment area is unlimited.”
5. Fire Compartment and Fire Wall
Article 18 uses the expression "fire separation" (yangın bölmesi). The definitions in Article 4 define fire compartment and fire wall:
“(tt) Fire compartment: the area within a building, including the ceiling and floor slab, separated on all sides into smoke- and heat-tight areas by structural elements resistant to fire for at least 60 minutes,”
“(rr) Fire wall: the vertical element that stops the progress and spread of fire for a determined period, between two buildings or, where spaces with different fire loads within the same building must be separated from one another,”
The compartment rules are in Article 24:
“(2) Walls shared by two or more buildings, and the walls and floors of enclosed areas with a fire hazard, such as the boiler room, car park, main electrical distribution rooms, transformer stations within the building, medium voltage stations and generator rooms, shall have the characteristics of a compartment wall.”
“(7) For fire compartments to be effective, the fire resistance of the elements surrounding the compartment shall also be continuous at the junction points, and there shall be no openings lacking fire resistance between compartments.”
Openings in a fire wall are regulated in Article 25:
“(2) There shall be no holes or openings in fire walls. Where it is not possible to avoid openings such as doors and fixed light windows in the walls, these shall be fire resistant for at least half the duration of the fire wall's resistance. Doors must be self-closing and smoke-tight.”
Fourth paragraph of Article 62, for lifts descending to basement floors and lobbies in front of car parks:
“Lifts that also serve the basement floors must be reached from a protected corridor or a fire safety lobby on the basement floors. The doors of lifts cannot open directly into usage areas other than corridors, lobbies and similar areas. (Additional sentence: 16/3/2015-2015/7401 Decision) Where a lobby is formed with laminated glass in front of lifts and escalators to car parks, the car park section and the glass shall be protected by a sprinkler system.”
For car parks and other sprinkler thresholds, see our article on when a sprinkler is mandatory.
6. Opinion in Case of Doubt: Art. 5(3)
Besides Article 8(2) on the occupancy class, the general rule for cases of doubt is in Article 5:
“(3) In the implementation of this Regulation, on matters of doubt relating to design and construction, the written opinion of the Ministry of Environment, Urbanisation and Climate Change shall be obtained as the basis for implementation, and on other matters the written opinion of the Ministry of Interior, and action shall be taken in accordance with these opinions.”
For projects, the fourth paragraph of Article 6:
“Projects are implemented after being approved by the authorities competent to issue licences. On matters that need interpretation, clarification or are ambiguous, action and implementation shall follow after obtaining the opinion of the Ministry of Environment, Urbanisation and Climate Change.”
7. Link with the Business Licence
Article 5 of the Fire Regulation ties the operating licence to works compliant with the regulation in buildings whose intended use is changed:
“Where it is determined that, in newly built buildings or buildings whose intended use is changed by a project modification, the works have not been carried out according to the principles laid down in this Regulation, no occupancy permit or operating licence shall be issued for the building until these deficiencies are remedied.”
If the intended use of existing buildings is changed to a healthcare building, the first paragraph of Article 138 excludes these buildings from the part on existing buildings; under Article 139, the provisions in the other parts of the Regulation apply to them:
“(1) The provisions set out in the other parts of this Regulation shall apply to those existing buildings whose intended use has been changed after the entry into force of this Regulation and which are listed in the first paragraph of Article 138.”
In the İşyeri Açma ve Çalışma Ruhsatlarına İlişkin Yönetmelik (Regulation on Business Opening and Operating Licences), the businesses from which a fire brigade report is requested are listed in point 5(h). For details, see our article on who is asked for a fire brigade report. For licence periods, we also have an article on statutory time limits for the business licence.
A business opening and operating licence is submitted in a sales center application. For the application file, see our article on the sales center authorization certificate application file; for help with the application, see sales center authorization certificate application support is also available.
8. Frequently Asked Questions
What does mixed-use building mean?
It is one of the occupancy classes listed in Article 8 of the Fire Regulation. Under Article 18, if sections of different classes cannot be separated by a suitable fire compartment, or separate measures cannot be applied because they are interlocked, the rules requiring higher protection apply to the whole building.
Is an office building with a shop on the ground floor treated as a commercial building?
Under the second paragraph of Article 13, small commercial sections in a building that primarily falls into another occupancy class are subject to the provisions on the primary occupancy classification of the building.
Which class does a doctor's office fall into?
Article 12 counts the offices of doctors and dentists among office buildings. Under point (b) of Article 11, private clinics, diagnosis and treatment centres and medical laboratories are counted as healthcare buildings.
What happens if there is doubt about the occupancy class?
Under the second paragraph of Article 8, the assessment and decision of the Ministry of Environment, Urbanisation and Climate Change shall be followed.
Is a small storeroom in a building treated as a separate class?
Under the second paragraph of Article 16, storage sections smaller than 50 m² within a building are considered part of the main building.